ALME

Brand: DAB
Brand: Italy

APPLICATIONS
Hot or cold water circulation pump with in-line ports, suitable for installation directly on the pipework of on civil and industrial heating, air conditioning, refrigeration, and sanitary water plants. Particularly versatile thanks to the use of the MCE/C inverter, offering performance features capable of
automatically adapting to the different needs of the system, keeping a consistent differential pressure.

TECHNICAL DATA

Operating range: from 1 to 8,4 m³/h with head up to 21 metres.
Liquid temperature range: from -15 °C to +120 °C.
Pumped liquid: clean, free of solids and abrasives, non-viscous, nonaggressive, non-crystallised and chemically neutral, with properties similar to water.
Maximum, glycol content 30% (for other glycol percentages contact Technical Support).
Installation: fixed, horizontal position.
Maximum ambient temperature: +40 °C.
Maximum operating pressure: 10 bar (1000 kPa).
Protection class: IP 55.
Insulation class: F.
Standard voltage: single-phase 220-240 V, 50/60 Hz.

CONSTRUCTION FEATURES OF THE PUMP

Pump body and motor support in cast iron. 2″ M-GAS suction and delivery ports. Technopolymer impeller. Carbon/ceramic mechanical seal. Construction features of the motorM External ventilation cooling, closed, asynchronous type, with four poles for the ALM version, and two poles for the ALP version. Rotor running on permanently lubricated ball bearings, oversized to ensure low noise and durability. Construction according to CEI 2-3.

Flow1m³/h - 8.4m³/h
HeadUp to 21m
Max. Operating Pressure10 bar
Single Phase 220-240 V, 50/60 Hz
Pumped liquidclean, free of solids and abrasives, non-viscous, nonaggressive, non-crystallised and chemically neutral, with properties similar to water. Maximum, glycol content 30%
Temparature Range-15⁰C - +120⁰C
Max. Ambient Temparature +40 °C
Protection ClassIP 55
Insulation ClassF